SUDS — Soap Usage & Dispensing System
Four-tank water quality monitoring with automated dosing at a fraction of vendor cost.
01
Problem
Electrostatic-dissipating soap in the glass washer was causing static-shock incidents on the line. Early conductivity sensing was unusable: the same supply that drove the probes also collapsed under load, so readings looked like process swings when they were really voltage drop and coupled noise.
02
Approach
I treated it as a measurement problem before a software problem. Star grounding came first. Then Atlas Scientific conductivity modules got their own isolated supply and differential wiring into a Revolution Pi, with Python normalizing tank data for an Ignition Perspective dosing view.
SUDS installation
03
Architecture
Four washer tanks feed isolated Atlas Scientific conductivity modules. Independent 5 V rails and differential pairs land on the RevPi; Perspective only sees cleaned engineering units and dose commands.
04
Implementation
The edge script never trusts a raw UART line. It rejects probe chatter, converts microsiemens to a tank state, and only then writes tags the Perspective application uses for alarming and dose control.
# Isolated 5 V rail + differential pair into the RevPi UART
PROBE_ERROR_PREFIXES = ("*", "ERROR")
def read_conductivity(uart):
uart.write(b"R\r")
line = uart.readline().decode("ascii", errors="ignore").strip()
if not line or line.startswith(PROBE_ERROR_PREFIXES):
return None
us_cm = float(line)
if us_cm < 0:
return None
return us_cm
def tank_state(us_cm, low, high):
if us_cm is None:
return "fault"
if us_cm < low:
return "dose"
if us_cm > high:
return "high"
return "ok"
05
Results
06
Reflection
What I’d do next
Next I would add a commissioning screen that graphs supply voltage next to conductivity so the next technician can see grounding issues in minutes, and store dose totals per tank for soap usage reporting.